Glossary of terms used in standby battery monitoring & service


Battery

The total DC back-up power system provided by an arrangement of strings in either series, or series / parallel connections depending on voltage / capacity required.


Bloc

Short for monobloc


Cell (lead-acid)

An electrochemical cell, nominally 2 volts.


Cell (Nickel Cadmium)

An electrochemical cell, nominally 1.2 volts.


Complex Impedance

In battery terms complex impedance may be defined as the separate electrical elements of an cell, i.e. series resistance, parallel resistance, inductance and capacitance, the determination of which give insight into the cell electrochemical processes.


Electrolyte

A solution of sulfuric acid and water which conducts current through the movement of ions (charged particles in the electrolyte solution) between positive and negative plates. It supplies sulfate ions for reaction with the active material of both positive and negative plates.


Grids

A lead alloy framework that supports the active material of a battery plate and conducts current.


GEL

Another type of sealed monobloc where the electrolyte is held in a gel matrix. Performance is similar (though not identical) to that of VRLA.


GSM

Global System for Mobile communications


Hold Up Time (Autonomy)

The time period for which the battery is expected to deliver its specified current.


Intercell connections

Connections between the straps of two cells, positive of one cell to the negative of the next.


Monobloc

One or more (lead-acid) cells in a single enclosure, with one positive and one negative post / terminal, consisting of one or more electrochemical cells in series, with a total terminal potential of 2, 4, 6 or 12 volts nominal.

Note: In order to provide flexibility, some manufacturers bring out more than two terminals.


OCS

Overview & Control System; can be any equipment which can collate and analyze battery data, and in some cases visualize battery performance. Such equipment includes a dedicated Battery Monitor, PC, Building Management System, SCADA system, UPS or Intelligent Charger.


Open Circuit Voltage (OCV)

The voltage of a battery when it is not delivering or receiving power. It is 2.11 volts for a fully charged battery cell.


Plates

Flat, typically rectangular components that contain the active material and a mechanical support structure called a grid, which also has an electrical function, carrying electrons to and from the active material. Plates are either positive or negative, depending on the active material they hold.


Primary Supply System

The normal source of power for the load, usually AC mains.


PSTN

Public Service Telephone Networks


Separators

Porous plastic, electrically insulating sheets which allow transfer of ions between plates, but prevent physical contact between plates and resulting electronic conduction.


‘Simple’ Impedance

Although strictly all impedance are complex, in battery testing terms the ‘simple impedance’ is defined as the AC resistance of the bloc under test at a single frequency defined by RMS Vac / Iac, or similar calculation.


SoH

State of Health


SoC (1)

System on Chip (single integrated circuit)


SoC (2)

State of Charge


Standby System

The emergency back-up power source in the event of a Primary Supply System failure.


Straps or Group Bar

Lead alloy castings that connect a number of same polarity plates together in a cell and carry current.


String

An arrangement of blocs in series to give a specified terminal voltage and capacity.


Terminals

The electrical connection from the battery to the external circuit. Each terminal is connected to either the first (positive) or last strap (negative) in the series connection of cells in a battery.


Time To Run

In the event of supply failure, TTR is the calculated remaining time that the battery will be able to supply the critical load. (Usually calculated to a specific VPC end voltage)


Vents

Components that allow gasses to exit the battery while retaining the electrolyte within the case. Can be permanently fixed to the cover or removable, depending on battery design.


VPC

The potential difference between positive and negative terminals of a single electrochemical cell, nominally 2 volts. In a monobloc, VPC will be the nominal terminal voltage divided by the number of cells in the bloc. (i.e. in a nominally 12V bloc it is 12/6 = 2V)


VRLA, SLA, AGM

Valve Regulated Lead Acid, Sealed Lead Acid, Activated Glass Mat; A ‘reduced maintenance’ type of sealed monobloc, using recombination technology to avoid major electrolyte losses through gassing. The electrolyte is minimal, typically only moisture wicked into glass pads. A valve is provided to prevent a build-up of pressure in case of over charge.


VLA, FLA

Vented Lead Acid, Flooded Lead Acid; Traditional types of cells with liquid electrolyte, utilizing clear glass or plastic cases.