HOxx-P-

7 ranges: 60 ARMS, 100 ARMS, 120 ARMS, 150 ARMS, 180 ARMS, 240 ARMS, 250 ARMS. Overcurrent detection on a dedicated pin, Short response time, Access to voltage reference, Low offset and gain drift, Measuring range up to 2.5 x IPN, Small design (22 (W) x 43 (L) x 30 (H)), High accuracy at 25°C: 1% of IPN & at 105°C: 4.6% of IPN, Creepage & clearance distances: 8 mm + CTI 600

Model details

HO 120-P-0100

120 ARMS, Overcurrent detection set @ 2.93 x IPN on a dedicated pin,Short response time: 3.5 µs,Access to voltage reference 2.5 V

Series
HOxx-P-
Measurement
Current
Nominal Value
120 A
Measuring Range
300 A
Second. Nominal Signal
Voltage
Second. Nominal Signal Value
Instantaneous 2.5 +/- 0.8 V
Primary Signal
AC + DC
Supply Voltage
External DC Unipolar
Supply Voltage Range
5 - 5 V
Accuracy
1 %
Op. Temperature
-40 °C / 105 °C
Technology
Open loop Hall effect
Mounting
PCB
Applications
Drives
Power Supplies
Renewable Energies
Welding
HO 120-P-0100
PICTURE
FRONT
BACK
LEFT
RIGHT
Order

Contact Information

Series

Product of the same series

HO 150-P-0100

150 ARMS, Overcurrent detection set @ 2.93 x IPN on a dedicated pin,Short response time: 3.5 µs,Access to voltage reference 2.5 V

HO 60-P-0100

60 ARMS, Overcurrent detection set @ 2.93 x IPN on a dedicated pin,Short response time: 3.5 µs,Access to voltage reference 2.5 V

HO 250-P-0100

250 ARMS, Overcurrent detection set @ 2.93 x IPN on a dedicated pin,Short response time: 3.5 µs,Access to voltage reference 2.5 V

HO 240-P-0100

240 ARMS, Overcurrent detection set @ 2.93 x IPN on a dedicated pin,Short response time: 3.5 µs,Access to voltage reference 2.5 V

HO 180-P-0100

180 ARMS, Overcurrent detection set @ 2.93 x IPN on a dedicated pin,Short response time: 3.5 µs,Access to voltage reference 2.5 V

HO 100-P-0100

100 ARMS, Overcurrent detection set @ 2.93 x IPN on a dedicated pin,Short response time: 3.5 µs,Access to voltage reference 2.5 V