Industrie
| Nominalstrom Messberich IpN (A) |
Versorgung (V) |
Typische Genauigkeit @ 25°C % von IpN |
Bandbreite (kHz) |
Einbau |
Technologie | Serie |
| 0.1 - 0.4 | +/-15 | 2% | DC - 18 | PCB | Fluxgate | CT xxx -P |
| 0.25 - 200 | +/- 12...15 | 0.41 - 0.85% | DC - 200 | PCB | C/L | LA 25-200 -P |
| 2 - 100 | +5 | 3 - 8% | DC - 105 | PCB | O/L | FHS 40-P/SP600 |
| 3 - 50 | +/-12...15 SP2 + 12...15 |
1 - 2% | DC - 50 | PCB | O/L | HX & HX/SP2 |
| 5 - 50 | + 5 | 1% | DC - 50 | PCB | O/L | HXS |
| 5 - 50 | +/-15 SP1 +5 |
1 - 4% | DC - 50 | PCB | O/L | HY & HY/SP1 |
| 6 - 25 | + 5 | 0.7% | DC - 200 | PCB | C/L | LTS - LTSR - LTSP |
| 16 - 100 | +/- 12...15 | 0.9% | DC - 300 | PCB | C/L | LAX 100-NP |
| 25 - 125 | +/- 12...15 | 0.25 - 0.4% | DC - 200 | PCB | C/L | LAH |
| 50 - 100 | + 5 | 1 - 1.7% | DC - 100 | PCB | Eta | LAS |
| 50 - 100 | +/- 15 | 1 -2.2% | DC - 50 | PCB | O/L | HTY |
| 50 - 400 | + 5 | 1% | DC - 50 | PCB | O/L | HAIS |
| 50 - 400 | +/- 12...15 | 1% | DC - 50 | PCB | O/L | HTB |
| 50 - 400 | +/-12...+15 | 1.75% | DC - 50 | PCB | O/L | HTB/SP5 |
| 50 - 600 | +/- 15 | 1 -1.75% | DC - 50 | Panel | O/L | HAL |
| 50 - 600 | +/- 15 | 1 - 3% | DC - 50 | Panel/PCB | O/L | HAS |
| 100 - 800 | +/- 15 | 1 - 2.7% | DC - 50 | PCB | O/L | HAC |
| 100 - 1000 | +/- 15 | 1 - 1.75% | DC - 50 | Panel | O/L | HTA |
| 1000 - 10000 | +/- 12...60 0...+24 |
0.2 - 0.8% | DC - 150 | Panel | C/L | LT |
| 200 - 500 | +/-12...18 | 0.3% | DC - 100 | Panel | C/L | LA 205 / 305 -S/ -T |
| 200 - 800 | +5 Note: offset rationetric |
1% | DC - 20 | PCB | O/L | HTFS |
| 200 -2000 50 - 500 |
+/- 12..15 | 2.2 - 3.25% | DC - 4 --10 | Panel Split Core |
O/L | HOP-HTR |
| 200 - 2000 | +/-12...24 | 0.2 - 0.4% | DC - 150 | PCB/Panel | C/L | LF |
| 300 - 400 | +/-15 | 0.7 - 1% | DC - 50 | Panel | C/L | LA 306-S |
| 500 - 1500 | +/- 15 | 1 - 1.75% | DC - > 25 | Panel | O/L | HAT |
| 500 - 2500 | +/- 15 | 1 -3.25% | DC - > 25 | Panel | O/L | HAX |
| 4000 - 20 000 | +/- 15 | 1% | DC - 3 | Panel | O/L | HAZ |
| 1 - 100 | +/- 15 | <0.25% | 500 | Panel | Fluxgate C | CT |
| 150 - 600 | +/- 15 | <0.005% | 100 | Panel | Fluxgate IT | IT |
| 300 | +/- 15 | <0.05% | 100 | Panel | Fluxgate IT | ITB 300-S |
| 400 | +/- 15 | <0.0033% | 100 | Panel | Fluxgate IT | IT 400-S |
| 700 | +/- 15 | <0.0053% | 100 | Panel | Fluxgate IT | IT 700-S |
Die Angaben gelten nur als allgemeine Hinweise. Bitte beachten Sie das spezifische Datenblatt für jedes Produkt.
Spannungsmessungen in Industrie und Traktion
Mit R1 Widerstand
| Nominalstrom Messberich VPN (V) |
Versorgung(V) | Typische Genauigkeit @ +25°C % von VPN |
Bandbreite (kHz) |
Einbau |
Technologie | Serie |
| 50 - 2000 | +/- 12...24 | 0.7 | <13 | Panel | Isolation Amplifier |
AV 100-Voltage |
| 50 - 2000 | +/- 15...24 | 0.7 - 1.2 | <10 | Panel | C/L | LV 100-Voltage 1 |
| 200- 1200 | +/- 12...15 |
0.8 - 0.9 |
<10 | Panel | C/L | LV 25-Voltage |
| 85 -1400 | +/- 15...24 | <0.375 | <300-800 | Panel | Fluxgate C | CV 3-Voltage |
| 200 - 6400 | +/- 15...24 | 0.8 - 2.5 | <1 | Panel | C/L | LV 200- AW/2/Voltage |
| 2500 - 4000 | +/- 15...24 | 0.2 - 0.8 | <10 | Panel | C/L | LV 100-Voltage2 |
| 2121 - 4242 | +/- 15 % +/- 24 | <1.4 | <21 | Panel | Fluxgate C | CV 4-Voltage |
Ohne R1 Widerstand
| Nominalstrom Messberich IPN (VPN) |
Versorgung(V) | Typische Genauigkeit @ +25°C % von IPN |
Bandbreite (kHz) |
Einbau |
Technologie | Serie |
| 10 mA (10 - 500V) |
+/- 12...15 | 0.8 - 1 | <10 | PCB | C/L | LV 25-P |
| 10 -210mA (100 - 2500V) |
+/- 12...24 | 0.7 | <10 | Panel | C/L | LV 100 |
| 20 mA (100 - 2500V) |
+/- 15...24 | 0.6 | <6 | Panel | C/L | LV 200-AW/2 |