HOYL

High performance, contactless current transducers for DC, AC and pulse currents measurements of 200 A, 400 A, 600 A, and 800 ARMS nominal with galvanic isolation. For mounting on busbar with large aperture (40 x 13 mm). Overcurrent detection set @ 2.93 x Ipn on a dedicated connection. Short response time: 3.5 µs. Access to voltage reference. Low offset and gain drift. Measuring range up to 2.5 x Ipn. Small design (35 (W) x 71 (L) x 50 (H)). Accuracy at 25°C: 1% of Ipn, at 105°C: 3.8% of Ipn. Creepage & clearance distances: 10.5 mm + CTI 600. Single supply 0, +5 V or 0, +3.3 V. Operating temperature range: -40°C to +105°C. Voltage output (0.8 V @ Ipn). Secondary connections on JST B05B-PASK connector. Bandwidth DC... 140 KHz (-3 dB).

Model details

HOYL 400-S-0100

400 ARMS nominal, Single supply + 5 V.

Series
HOYL
Measurement
Current
Nominal Value
400 A
Measuring Range
1000 A
Second. Nominal Signal
Voltage
Second. Nominal Signal Value
Instantaneous 2.5 +/- 0.8 V
Primary Signal
AC + DC
Supply Voltage
External DC Unipolar
Supply Voltage Range
5 - 5 V
Accuracy
1 %
Op. Temperature
-40 °C / 105 °C
Technology
Open loop Hall effect
Mounting
On primary fastening
Panel
Applications
Drives
Power Supplies
Renewable Energies
Welding
 HOYL 400-S-0100  HOYL
PICTURE
FRONT
BACK
LEFT
RIGHT
Download

Relative information

Order

Contact Information

Series

Product of the same series